The D400 GC diesel generator sets have been developed to meet your needs in standby applications. Producing reliable power of 400 ekW at 60 Hz, each generator set has been designed to meet ISO 8528-5 transient response requirements and built to accept 100 percent rated load in one step. Our D400 GC generator sets are engineered to EPA Stationary Emergency (Tier 3) emissions standards.
Compare Models
Generator Set Specifications
Minimum Rating
400 ekW
400 ekW
Maximum Rating
400 ekW
400 ekW
Emissions/Fuel Strategy
EPA Stationary Emergency
EPA Stationary Emergency
Voltage
480 to 600 Volts
480 to 600 Volts
Frequency
60 Hz
60 Hz
Speed
1800 rpm
1800 rpm
Duty Cycle
Standby
Standby
Engine Specifications
Engine Model
Cat® C13 In-line 6, 4-cycle diesel
Cat® C13 In-line 6, 4-cycle diesel
Bore
5.1 in
130.0 mm
Stroke
6.2 in
157.0 mm
Displacement
763.0 in³
12.5 B
Compression Ratio
16.3:1
16.3:1
Aspiration
Turbocharged Air-to-Air Aftercooled
Turbocharged Air-to-Air Aftercooled
Fuel System
MEUI
MEUI
Governor Type
ADEM™A4
ADEM™A4
Generator Set Dimensions
Length - Maximum
182.8 in
4625.0 mm
Width - Maximum
64.2 in
1630.0 mm
Height - Minimum
80.3 in
2039.0 mm
Height - Maximum
96.7 in
2456.0 mm
Dry Weight - Genset (minimum)
7330.4 lb
3325.0 kg
Dry Weight - Genset (maximum)
4107.0 lb
9054.4 kg