Menu

Providing reliable energy solutions ,our C7.1 diesel generator sets are made to meet your standby and prime three phase applications. All standby C7.1 generator sets are supplied with 4 years extended service coverage as standard. We've designed each to ISO 8528-5 transient response requirements. C7.1 generator sets are available with a choice of emissions levels. We offer easy-to-use Cat control panels, EMCP 4.1 or EMCP 4.2 options. Browse a broad range of accessories including galvanised sound attenuated enclosures and integral fuel tanks. Our C7.1 generator sets are made for demands, so you can make yours.

Compare Models
Generator Set Specifications
expand / collapse icon
Minimum Rating 114 ekW 114 ekW
Maximum Rating 200 ekW 200 ekW
Emissions/Fuel Strategy U.S. EPA Cert,. Tier 3 U.S. EPA Cert,. Tier 3
Voltage 208 to 480 Volts 208 to 480 Volts
Frequency 60 Hz 60 Hz
Speed 1800 rpm 1800 rpm

Design Criteria

  • The generator set is designed to meet ISO8528-5 transient response and NFPA 110.
  • Cooling system designed to operate in 50˚C / 122˚F ambient temperatures with an air flow restriction of 0.5 in. water

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

Generator

  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • IP 23 Protection

EMCP Control Panel

The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. The EMCP 4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP 4 systems can be further customized to meet your needs through programming and expansion modules. The EMCP4.1 is fitted as standard

World Wide Product Support

Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products

Single-Source Supplier

Fully prototype tested with certified torsional vibration analysis available

CE Certification

CE Certification available

General

  • Single wall 8 hour wide fuel tank
  • Circuit breaker, IEC, 3 pole
  • Industrial Silencer (10 dBA)

C7.1 Tier 4 (60 Hz) Standard Equipment

Air Inlet System
expand / collapse icon
  • Air Cleaner; light duty with disposable element

C7.1 Tier 4 (60 Hz) Optional Equipment

Alternator System
expand / collapse icon
  • Anti-condensation heater
  • 3 Phase sensing
  • Alternator removal
  • Optional LC frame alternators
  • Quatrature droop king
  • R frame auxiliary winding: R2273L4 SE aux alt 07, aux alt 08 and aux alt 10
  • Optional LC frame alternator with coastal insulation protection
  • Permanent magnet