Providing reliable energy solutions ,our C7.1 diesel generator sets are made to meet your standby and prime three phase applications. All standby C7.1 generator sets are supplied with 4 years extended service coverage as standard. We've designed each to ISO 8528-5 transient response requirements. C7.1 generator sets are available with a choice of emissions levels. We offer easy-to-use Cat control panels, EMCP 4.1 or EMCP 4.2 options. Browse a broad range of accessories including galvanised sound attenuated enclosures and integral fuel tanks. Our C7.1 generator sets are made for demands, so you can make yours.

Generator Set Specifications

  • Minimum Rating 114 ekW 114 ekW
  • Maximum Rating 200 ekW 200 ekW
  • Emissions/Fuel Strategy U.S. EPA Cert,. Tier 3 U.S. EPA Cert,. Tier 3
  • Voltage 208 to 480 Volts 208 to 480 Volts
  • Frequency 60 Hz 60 Hz
  • Speed 1800 rpm 1800 rpm

Engine Specifications

  • Engine Model C7.1 I-6, 4-Cycle Diesel C7.1 I-6, 4-Cycle Diesel
  • Displacement 427.8 in³ 7.01 l
  • Fuel System Common Rail Common Rail
  • Aspiration Turbocharged, Air to Air Aftercooled Turbocharged, Air to Air Aftercooled
  • Governor Type ADEM™A4 ADEM™A4
  • Compression Ratio 16.5:1 16.5:1
  • Bore 4.13 in 105.0 mm
  • Stroke 5.31 in 135.0 mm

Generator Set Dimensions

  • Length - Maximum 98.4 in 2500.0 mm
  • Width - Maximum 52.0 in 1320.0 mm
  • Height - Maximum 64.0 in 1626.0 mm

Design Criteria

  • The generator set is designed to meet ISO8528-5 transient response and NFPA 110.
  • Cooling system designed to operate in 50˚C / 122˚F ambient temperatures with an air flow restriction of 0.5 in. water

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

Generator

  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • IP 23 Protection

EMCP Control Panel

The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. The EMCP 4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP 4 systems can be further customized to meet your needs through programming and expansion modules. The EMCP4.1 is fitted as standard

World Wide Product Support

Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products

Single-Source Supplier

Fully prototype tested with certified torsional vibration analysis available

CE Certification

CE Certification available

General

  • Single wall 8 hour wide fuel tank
  • Circuit breaker, IEC, 3 pole
  • Industrial Silencer (10 dBA)

C7.1 Tier 4 (60 Hz) Standard Equipment

Air Inlet System

  • Air Cleaner; light duty with disposable element

Control Panels

  • EMCP 4.1

Cooling System

  • Fan drive, battery charging alternator drive
  • Radiator and cooling fan with guards
  • Caterpillar extended life coolant
  • Coolant drain line with valves

Exhaust System

  • Stub pipe, gaskets, raincap and SAE exhaust flange for customer use; shipped loose

Fuel System

  • Standard open set fuel tank / base supplied
  • Base, formed steel with single wall integral 8-hour fuel tank

Generator and Generator Attachments

  • Voltage regulator (single phase sensing)
  • 12 leads
  • IP23 protection
  • Circuit breaker, IEC, 3 pole, mounted in tower panel
  • Segregated low voltage (AC/DC) wiring panel
  • Tower panel, IP22, bottom cable entry

Starting / Charging System

  • 24V battery with rack and cables

Governing System

  • Mechanical and electrical governing system - model dependent

Lube System

  • Lubricating oil
  • Oil drain line with valve

Mounting System

  • Includes lifting provision and drag points
  • Captive linear vibration isolators between base and engine-generator
  • Termination points for coolant and lube oil drain lines

General

  • Engine and alternator pre-paint, Caterpillar Yellow

C7.1 Tier 4 (60 Hz) Optional Equipment

Alternator System

  • Anti-condensation heater
  • 3 Phase sensing
  • Alternator removal
  • Optional LC frame alternators
  • Quatrature droop king
  • R frame auxiliary winding: R2273L4 SE aux alt 07, aux alt 08 and aux alt 10
  • Optional LC frame alternator with coastal insulation protection
  • Permanent magnet

Circuit Breakers

  • 4 Pole 250A, 400A and 630A Circuit Breakers
  • Padlockable breaker device

Control Panel Options

  • Earth fault (2 wire only)
  • Control panel heater
  • Battery charger
  • Earth leakage (2 wire only)
  • Speed adjust contacts
  • Volt free contacts
  • Overload shutdown via breaker
  • Emergency stop with key
  • Speed adjust potentiometer
  • Panel mounted audible alarm

Cooling System

  • Low coolant level shutdown
  • Coolant heater
  • Low coolant temperature

Control System

  • Volt free contacts for generator set running
  • Volt free contacts for common alarm
  • EMCP 4.2
  • Static battery charger
  • Control panel heater

Enclosures

  • Rental options (CAE only) - Socket blanking plate
  • Rental options (CAE only) - Single point lift
  • Rental options (CAE only) - Rental pack
  • Rental options (CAE only) - CEE form sockets for enclosure
  • Sound attenuated levels 1 and 2 enclosures

European Certifications

  • Upgrade to STD set for CE

Fuel Systems

  • Compact skidbase for open sets
  • Low fuel level alarm
  • DEFRA bunded fuel tank
  • Low fuel level shutdown
  • Open set narrow tankbase
  • Skidbase for CALG enclosure sets
  • High fuel level alarm

Mounting Options

  • Industrial silencer removal
  • Silencer installation kit
  • Electronic governor
  • Residential silencer
  • Battery removal

Test Reports

  • PGS test report @ 1.0 power factor
  • PGS test report @ 0.8 power factor

General

  • Stone guards / radiator trans flange

Global Certifications

  • Certification for CIS

Power Termination

  • Circuit breaker, IEC, 4 pole

Accessories / Miscellaneous

  • Packing case - canopied set
  • Packing case - compact set

Customer Stories

Discover what’s new and how customers like you are benefiting from our products and services. Check back often for updates.

Promotions

Looking for that perfect piece of used equipment to complement your fleet? Check out our Used Exclusives, featuring new machines every week!

Social

Let’s talk. Connect with us on one of our social channels to start the conversation and see what we’re up to.

Branch Locator

Looking for your nearest branch? Get in touch with us today by contacting one of our branches directly. We’re always ready to help.

Services

When you choose Finning, you have a wide array of support and specialty services to help you get the most from your equipment.

Technology

Integrated technology can help you understand your equipment's output and help extend its lifespan.

Finance

Choose from a range of financing solutions that allow you to purchase equipment, parts, services, and technology when you need it.