The Cat® spark-ignited generator product line for stationary applications feature permanent magnet excitation, amortisseur winding, skewed stator, voltage adjustment through the EMCP controller, Class H winding insulation and 2/3 pitch incorporated.

Generator Set Specifications

  • Frequency 60 Hz 60 Hz
  • Natural Gas Rating 200 eKW 200 eKW
  • Emissions/Fuel Strategy U.S. EPA Certified for Stationary Emergency Application U.S. EPA Certified for Stationary Emergency Application
  • Displacement 864.71 in 14.17 l
  • Fuel Type Natural Gas Natural Gas
  • Speed 1800 rpm 1800 rpm

Engine Specifications

  • Engine Model 14.2 L, Inline 6, 4 Cycle, Spark - Ignited 14.2 L, Inline 6, 4 Cycle, Spark - Ignited
  • Fuel System Carburetor, Down Draft Carburetor, Down Draft
  • Aspiration Turbocharged-Aftercooled Turbocharged-Aftercooled
  • Governor Type Electronic Electronic
  • Compression Ratio 9.5:1 9.5:1
  • Bore 5.31 in 134.87 mm
  • Stroke 6.5 in 165.1 mm

Generator Set Dimensions

  • Length 127.95 in 3250.0 mm
  • Width 52.93 in 1344.5 mm
  • Height 67.37 in 1711.2 mm
  • Weight 5756.0 lb 2610.9 kg

Engine

  • Four-stroke-cycle gas engine combines consistent performance and excellent fuel economy with minimum weight

Generator

  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency

EMCP Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Design Criteria

  • The generator set facilitates compliance with NFPA 110 and meets ISO 8528-5 requirements for transient response
  • Cooling system designed to operate in 50˚C/122˚F ambient temperatures with an air flow restriction of 0.5 in. water

UL 2200 / CSA - Optional

  • UL 2200 Listed packages
  • CSA Certified
  • Certain restrictions may apply
  • Consult with your Cat® Dealer

Worldwide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

DG200 GC (3 phase) Standard Equipment

Cooling

  • Closed coolant recovery system
  • Factory-installed radiator
  • 50/50 Ethylene glycol antifreeze
  • Radiator and cooling fan complete with protective guards
  • Standard ambient temperatures up to 50°C (122°F)

Air Inlet

  • Single element air filter

Fuel

  • Primary and secondary fuel shut-off
  • Low fuel pressure switch
  • Fuel pressure test po
  • Natural Gas or LP Vapor
  • NPT connection
  • Dual lock off valves

Exhaust

  • Exhaust outlet with 3” pipe

Generator

  • Permanent magnet excitation
  • Full load capacity alternator
  • Class H insulation material
  • Permanent magnet excitation
  • Integrated Voltage Regulator
  • Matched to the performance and output characteristics of Cat engines
  • Class H insulation material
  • Full load capacity alternator
  • IP23 Protection

Controls

  • EMCP 4.2 Series generator set controller

Mounting

  • Vibration isolaton (puck type)
  • Rubber vibration isolators

Electric Power - Package Serial Number Prefix

  • Battery charging alternator

Electric Starting and/or Prelube

  • Battery cables
  • Solenoid activated starter motor
  • Engine electrical system
  • Solenoid activated starter motor

Governor

  • Electronic governor (non adjustable)

Control Panel

  • EMCP 4.2 Series generator set controller

Starting/Charging

  • Batteries with rack and cables
  • 12 volt starting motor

DG200 GC (3 phase) Optional Equipment

Starting/Charging

  • Jacket water heater
  • Battery heater
  • Charging alternator
  • Battery charger – UL Listed 10 amp

General

  • Enclosures: sound attenuated, weather protective
  • Suitable for Use as Service Equipment (SUSE)
  • Automatic transfer switches (ATS)
  • UL 2200 package
  • CSA Certification

Generator

  • Thermal magnetic or electronic trip MCCBs
  • Anti-condensation heater
  • Shunt trip and auxiliary contact breaker
  • Anti-condensation heater
  • Excitation: [ ] Permanent Magnet Excited (PM)
  • Oversize and premium generators

Customer Stories

Discover what’s new and how customers like you are benefiting from our products and services. Check back often for updates.

Promotions

Looking for that perfect piece of used equipment to complement your fleet? Check out our Used Exclusives, featuring new machines every week!

Social

Let’s talk. Connect with us on one of our social channels to start the conversation and see what we’re up to.

Branch Locator

Looking for your nearest branch? Get in touch with us today by contacting one of our branches directly. We’re always ready to help.

Services

When you choose Finning, you have a wide array of support and specialty services to help you get the most from your equipment.

Technology

Integrated technology can help you understand your equipment's output and help extend its lifespan.

Finance

Choose from a range of financing solutions that allow you to purchase equipment, parts, services, and technology when you need it.