The 3516B diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. Producing reliable power from 1640 to 2250 ekW at 60 Hz, each generator set has been designed to meet ISO 8528-5 transient response requirements and to accept 100 percent rated load in one step. Our integrated control system keeps you connected through on-site and remote monitoring options. We offer easy-to-use EMCP control panel options, combining your management and diagnostic tools in one. The EMCP 4.4 controller provides multi-generator set paralleling capability, giving you the ability to add generator sets to match your growing power requirements. It's not just quality that matters but customization, choose from a broad range of accessories and bolt-on system expansion attachments. Find flexible packaging to fit unique spatial requirements and environmental conditions. Our 3516B generator sets are developed for such prerequisites, so that you can meet your specific power needs. For added safety select from one of the UL 2200 and CSA certified package options.

Generator Set Specifications

  • Minimum Rating 1640 ekW 1640 ekW
  • Maximum Rating 2250 ekW 2250 ekW
  • Emissions/Fuel Strategy Low fuel Consumption, Low Emissions Low fuel Consumption, Low Emissions
  • Voltage 220 to 4160 Volts 220 to 4160 Volts
  • Frequency 60 Hz 60 Hz
  • Speed 1800 rpm 1800 rpm
  • Duty Cycle Standby, Mission Critical, Prime, Continuous Standby, Mission Critical, Prime, Continuous

Engine Specifications

  • Engine Model C32 TA, V-12, 4-Stroke Water-Cooled Diesel C32 TA, V-12, 4-Stroke Water-Cooled Diesel
  • Bore 5.71 in 145.0 mm
  • Stroke 7.48 in 190.0 mm
  • Displacement 1958.7 in 32.17 l
  • Compression Ratio 15.0:1 15.0:1
  • Aspiration TA TA
  • Fuel System MEUI MEUI
  • Governor Type Adem™A4 Adem™A4

Generator Set Dimensions

  • Length - Maximum 234.5 in 5957.0 mm
  • Width - Maximum 90.0 in 2286.0 mm
  • Height - Maximum 98.2 in 2494.0 mm
  • Dry Weight - Genset (maximum) 30310.0 lb 13750.0 kg

3516B (60 Hz) with Upgradeable Package Standard Equipment

Air Inlet System

  • Air Cleaner; single element canister type

Control Panels

  • EMCP 4.2B
  • Emergency stop pushbutton
  • 24 Volt DC operation
  • Environmental sealed front face
  • Text alarm / event descriptions
  • Generator mounted - rear facing
  • Generator set packages include:
  • Caterpillar' s voltage regulator
  • IVR includes:
  • Reactive droop capability
  • 3 Phase voltage sensing
  • KVAR/PF modes
  • RFI suppression
  • Min / max exciter
  • Limiter and exciter diode monitor
  • Controls:
  • Speed adjust
  • Auto / start / stop control
  • Engine cool
  • Alarm acknowledge
  • Lamp test
  • Load histogram feature
  • PLC functionality
  • Customizable screens
  • 0 True RMS AC metering, 3-phase, +/-2% accuracy
  • Digital indication for:
  • RPM
  • DC volts
  • Operating hours
  • Oil pressure (psi, kPa or bar)
  • Coolant temperature
  • Volts (L-L & L-N)
  • Frequency (Hz)
  • Amps (per phase & average)
  • Power Factor (per phase & average)
  • kW (per phase, average & percent
  • kVA (per phase, average & percent)
  • kVAr-hr (total)
  • Warning / shutdown with common LED indication of shutdowns for:
  • Low oil pressure
  • High coolant temperature
  • Overspeed
  • Emergency stop
  • Failure to start (overcrank)
  • Low coolant temperature
  • Low coolant level
  • Programmable protective relaying functions:
  • Generator phase sequence
  • Over / under voltage (27/59)
  • Over / under frequency (81 o/u)
  • Reverse power (kW) (32) - Reverse reactive power (kVAr) (32RV) - Overcurrent (50/51)
  • Reverse reactive power (kVAr) (32RV) - Overcurrent (50/51)
  • Overcurrent (50/51)
  • Communications:
  • Customer data link (Modbus RTU)
  • Accessory module data link
  • Serial annunciator module data link
  • Cat Connect
  • 3 Analog inputs
  • 6 Customer programmable digital inputs
  • Number of I/O varies on options selected:
  • 4 Programmable relay outputs (Form A)

Lubrication System

  • Oil filter, filler and dipstick
  • Oil drain lines and valve
  • Fumes disposal
  • Lubricating oil
  • Gear type lube oil pump

Mounting System

  • Rails - engine/generator/radiator mounting
  • Anti-vibration mounts (shipped loose)
  • Rubber anti-vibration mounts (shipped loose)

Starting System

  • 24 Volt electric starting motor
  • 45 Amp charging alternator
  • Battery and battery rack w/cables
  • Battery disconnect switch

Literature

  • English

3516B (60 Hz) with Upgradeable Package Optional Equipment

Control System

  • EMCP 4.3, EMCP 4.4

Air Inlet System

  • Single element filter
  • Dual element air cleaner

Cooling System

  • Standard ambient radiators
  • Standard ambient ATAAC radiators
  • Optional installed radiators
  • Optional installed ATAAC radiators
  • Water level switch gauges
  • Coolant

Crankcase System

  • No explosion relief valves
  • Explosion relief valves
  • Ventilation system

Exhaust System

  • Elbows
  • Flange and exhaust expanders
  • Flanges
  • Flexible fittings
  • Y-Adapters
  • Mufflers
  • Exhaust offset
  • Tier 4 clean emissions module
  • Tier 4 dosing cabinet
  • Tier 4 clean emission MOD Kits
  • Clean emission parts

Fuel System

  • Primary Fuel Filter
  • Fuel Priming Pumps (Tier 4) - Manual or Electric

General

  • US aid emblem
  • Special paint (Colors other than Caterpillar yellow or high performance paints)

Generators and Attachments

  • Low / Medium voltage: 380, 440, 480, 600 volts, 3 phase 1800 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
  • Low / Medium voltage: 380, 416, 440, 480, 600, 2400, 4160 Volts, 3 Phase 1800 RPM, FW, PM, No. of Leads = 6, Pitch = .6667: 1600, 1800 Frame
  • High voltage: 6300, 6600, 6900 volts, 3 phase 1800 rpm, FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
  • High voltage: 12470, 13200, 13800 volts, 3 phase 1800 rpm,FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
  • Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
  • Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, PM, No. of Leads = 6, Pitch = .6667: 1600 and 1800 Frames
  • Space heater
  • Generator conversion
  • Thermostat for space heater
  • Alternator air cleaner
  • Differential current transformers (DCT)
  • Differential current transformers (DCT) 8.7 kV and 15 kV classes

Instrumentation

  • Pyrometer and Thermocouples

Lubrication System

  • Lube oil in standard sump
  • Oil level regulator
  • Prelube pumps

Mounting System

  • Puck style low efficiency isolators
  • Spring type vibration isolators
  • IBC vibration isolators

Power Connections

  • Ground cables between generator and terminal box
  • Neutral ground connections
  • Center post busbar
  • Right side power connections
  • Left side power connections
  • Rear power connections
  • 2700 Frame, four lead, four terminal
  • Low voltage circuit breakers

Special Tests / Reports

  • Canadian Standards Association certification
  • IBC certification
  • OSHPD certification
  • PGS test report @ 1.0 power factor
  • PGS test report @ 0.8 power factor
  • Standard engine test charge
  • generator test report
  • Fuel consumption test
  • Generator set fuel consumption test
  • Torsional vibration analysis reports

Starting and Charging

  • Engine barring device
  • 24 Volt battery set - Dry
  • 10, 20, 35 and 50 amp battery chargers
  • Electric starting motors
  • Air starting motors
  • Starter cover
  • Air pressure regulator
  • Jacket water heaters

Extended Service Coverage

  • Platinum, Gold and Silver coverage

News & Events

View the latest company and product news, events and customer stories.

Promotions

View the latest offers available on a range of Cat® equipment and genuine parts.

Social Media

Connect with us to learn more about our company, products, services and customers.

Branch Locations

With branches across the UK & Ireland, you can be sure that we’re never far away.

Services

Effectively manage your equipment to reduce operating costs and improve efficiency.

Technology

Integrated technology can help you understand your equipment's output and help extend its lifespan.

Finance

Quick and easy financing with customised payment plans through Cat Financial.

Please share your feedback on Finning.com!

Close window

We are committed to providing you with the best site experience possible.  Please take our brief survey to tell us how we are doing.

Thank you in advance for your time!