G3512 750 ekW

Emissions

EPA Certified for use in Emergency and Non-Emergency applications. Additional a NOx selectable genset is available to meets most worldwide emissions requirements down to 0.5 g/bhp-hr Nox level without aftertreatment

Full Range of Attachments

Wide range of bolt-on system expansion attachments, factory designed and tested Flexible packaging options for easy and cost effective installation

World Wide Product Support

Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠„ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products

CAT SR5 Generator

Designed to match performance and output characteristics of Caterpillar gas engines. Industry leading mechanical and electrical design. High efficiency

CAT EMCP4.3 Control Panel

The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4.3 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP4.3 systems can be further customized to meet your needs through programming and expansion modules.

Proven System

Field proven in a wide range of apllications worldwide, fully protype tested, and certified torsional vibration analysis available

CAT G3512 Gas Engine

Robust high speed block design provides prolonged life and lower owning operationg costs. Designed for maximum performance on low pressure pipeline natural gas. Simple open chamber combustion system for reliability and fuel flexibility. Leading edge technology in ignition system and air/fuel ratio control for lower emission and engine efficiency. One electronic control module handles all engine functions: ignition, governing, air/fuel ratio control and engine protection

CAT electronic control system

Simple user friendly interface and navigation. Digital monitoring, metering and protection setting. Fully-featured power metering and protective relaying. Remote control and monitor capability options

Select Units

Overview

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Generator Sets Specification

  • Gas Standby Rating 750 ekW 750 ekW

Generator Set Specifications

  • Fuel Type Natural Gas Natural Gas
  • Emissions/Fuel Strategy U.S. EPA Certified for Non-Emergency Stationary Genset U.S. EPA Certified for Non-Emergency Stationary Genset

Generator Sets Specifications

  • RPM 1800 rpm 1800 rpm
  • Frequency 60 Hz 60 Hz
  • Compression Ratio 9.7 9.7
  • Displacement 3173.0 52.0 l

Generator Set Dimensions

  • Length 205.7 in 5224.0 mm
  • Width 90.0 in 2286.0 mm
  • Height 99.4 in 2525.0 mm
  • Weight 27500.0 lb 12500.0 kg

Engine Specifications

  • Engine Model G3512 G3512
  • Displacement 3173.0 52.0 l
  • Aspiration TA TA
  • Bore 6.7 in 170.0 mm
  • Stroke 7.5 in 190.0 mm
  • Governor Type ADEM A4 ADEM A4

G3512 750 ekW Standard Equipment

Air Inlet

  • Two-element single-stage air cleaner with enclosure and service indicator

Control Panel

  • EMCP 4.3

Cooling

  • Jacket water and SCAC engine-driven pumps
  • Jacket water and SCAC thermostats
  • Package mounted radiator
  • LH or RG connections when radiator is not selected

Exhaust

  • Dry exhaust manifolds, insulated and shielded
  • Cat-flanged face outlet on turbocharger
  • Individual exhaust port and turbocharger outlet wired to integrated temperature sensing module (ITSM) with GCEM providing alarms and shutdowns

Fuel System

  • Throttle plate, 24V DC actuator, controlled by GECM
  • Fuel system is sized for 31.5 to 47.2 MJ/NM3 dry pipeline natural gas with pressure of 10.2 to 34.5KPa to the engine fuel control valve
  • Engine-installed electronic control valve
  • 24V DC energized-to-run (ETR) gas shutoff valve
  • Gas pressure regulator

General

  • Paint- Caterpillar Yellow except rails and radiators gloss black 
  • “Stationary Use Only” Label in Correspondence with EPA Nonroad Mobile SI rule 
  • Parts book
  • Crankshaft vibration damper and guard
  • Operation and maintenance manuals
  • RH Service

Generator

  • SR5
  • Permanent Magnet Excitiation
  • Caterpillar's Digital Voltage Regulator (CDVR) including reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, and a min/max exciter
  • Anti-condensation space heater
  • Winding temperature detectors
  • NEMA Class H insulation

Governing System

  • ADEM A4

Ignition System

  • Electronic Ignition System (controlled by ADEM A4) 
  • Individual Cylinder Detonation Sensitive Timing (DST) 

Starting/Charging

  • Electric Starter

G3512 750 ekW Optional Equipment

Air Inlet

  • Mounting brackets and piping
  • Air cleaner with precleaner

Circuit Breakers

  • Right, left, rear mounted
  • 3-pole (IEC 947-2 rated)
  • 100% rated, 3-pole (UL/CSA/IEC) 5th Digit Rating
  • S LSI, G LSIG, P LSIG-P, 4th Digit Type
  • 1200A, 3 Pole, UL-100% Rated P-Frame Circuit Breakers
  • 1600A, 2000A 3 Pole, UL-100% Rated R-Frame Circuit Breakers
  • 2000A 3 Pole, UL-100% Rated Masterpact Circuit Breakers
  • Frame mounting

Control Panel

  • Local alarm module
  • Remote annunciator
  • Local PC monitoring
  • Remote PC monitoring
  • Engine failure relay

Cooling

  • Remote radiator for JW and SCAC circuits, level switch included but not wired
  • Coolant level drain line with valves, fan with guard
  • Inlet/Outlet connections

Exhaust

  • 305 mm (12 in.) muffler
  • 18, 25 dBA Attenuation
  • 305mm (12 in) spark arresting muffler
  • 305 mm (12in.) elbow
  • 305 mm (12 in.) flange
  • Flexible fittings

Fuel System

  • 3, 0-100 kPag, 4-20mA gas train pressure sensors

General

  • US AID emblem
  • Special paint order
  • Tool set
  • Digital diagnostic tool

Generator

  • Cable access box
  • Bearing temperature detectors
  • Generator air filter
  • Low voltage extension box
  • European bus bars

Starting/Charging

  • 24V starting motors
  • Battery with cables and rack (shipped ;ppse_
  • Jacket water heater
  • 45A, 24V charging alternator (requires engine driven pumps)
  • 20A, 24VDC battery charger

News & Events

View the latest company and product news, events and customer stories.

Promotions

View the latest offers available on a range of Cat® equipment and genuine parts.

Social Media

Connect with us to learn more about our company, products, services and customers.

Branch Locations

With branches across the UK & Ireland, you can be sure that we’re never far away.

Services

Effectively manage your equipment to reduce operating costs and improve efficiency.

Technology

Integrated technology can help you understand your equipment's output and help extend its lifespan.

Finance

Quick and easy financing with customised payment plans through Cat Financial.

Please share your feedback on Finning.com!

Close window

We are committed to providing you with the best site experience possible.  Please take our brief survey to tell us how we are doing.

Thank you in advance for your time!