Menu

CTG Series Automatic Transfer Switch

Select Units

Overview


The Cat® CTG Series Automatic Transfer Switches (ATS) are pre-configured for applications requiring the dependability and ease of operation found in a full feature power contactor type transfer switch.

CTG switches are equipped with the next generation MX150 microprocessor panel, which controls the operation and displays the status of the transfer switch's position, timers and available sources. As an embedded digital controller, the MX150 offers high reliability and ease of unattended operation across a range of applications.

Technical Summary

  • Rating Range 40-3000A 40-3000A
  • Switch Type Contactor based Contactor based
  • Transfer Type Open transition Open transition

Features

  • Ratings 40 to 3000 amps (2, 3 or 4 poles)
  • UL 1008 listed at 480 VAC
  • CSA certified at 600 VAC (200-225 amp - 480V)
  • IEC listed at 480 V
  • Double throw, mechanically interlocked contactor mechanism
  • Electrically operated, mechanically held
  • Designed for emergency and standby applications
  • Available in standard open transition (CTG)or delayed transition (CTGD) models
  • Ringing wave immunity per IEEE 472 (ANSI C37.90A
  • Conducted and Radiated Emissions per EN55022 Class B (CISPR 11) (Exceeds EN55011 & MILSTD 461 Class 3)
  • ESD immunity test per EN61000-4-2 (Level 4)
  • Radiated RF, electromagnetic field immunity test per EN61000-4-3 (ENV50140) 10v/m
  • Electrical fast transient/burst immunity test per EN61000-4-4
  • Radiated RF, electromagnetic field immunity
  • Surge immunity test per EN61000-4-5 IEEE C62.41 (1.2 X 50 ms, 5 & 8 kV)
  • Conducted immunity test per EN61000-4-6 (ENV50141)
  • Voltage dips and interruption immunity EN61000-4-11
  • Seismic Compliance to IEEE-693-2005 and IBC-2003

Design and Construction Features

  • Close differential 3 phase under-voltage sensing of the normal source - factory standard setting 90% pickup, 80% dropout (adjustable);under frequency sensing of the normal source factory setting 95% pickup (adjustable)
  • Voltage and frequency sensing of the emergency source - factory standard setting 90% pickup voltage, 95% pickup frequency (adjustable)
  • Test switch (fast test/load/no load) to simulate normal source failure - automatically bypassed should the emergency source fail
  • Type 1 enclosure is standard - also available in open style or Types 3R, 4, 4X, or 12
  • News & Events

    View the latest company and product news, events and customer stories.

    Promotions

    View the latest offers available on a range of Cat® equipment and genuine parts.

    Social Media

    Connect with us to learn more about our company, products, services and customers.

    Branch Locations

    With branches across the UK & Ireland, you can be sure that we’re never far away.

    Services

    Effectively manage your equipment to reduce operating costs and improve efficiency.

    Technology

    Integrated technology can help you understand your equipment's output and help extend its lifespan.

    Finance

    Quick and easy financing with customised payment plans through Cat Financial.

    Please share your feedback on Finning.com!

    Close window

    We are committed to providing you with the best site experience possible.  Please take our brief survey to tell us how we are doing.

    Thank you in advance for your time!