Producing reliable power from 2500 kVA to 2750 kVA at 50 Hz, our 3516C diesel generator sets are made to match your mission critical, continuous, standby and prime applications, and meet our quality standards. We've engineered each to ISO 8528-5 transient response requirements and to accept 100 percent rated load in one step. Depending on the model, 3516C generator sets are EPA Stationary Emergency (Tier 2) or Tier 4 Interim certified. Industry leading innovation means our Tier 4 Interim models have emissions reduced up to 90 percent — it's technology that has benefits beyond today. Seismic certification is also available for select models, maintaining power after unexpected disturbances. The integrated control system, including ATS and switchgear, ensures a consistent power supply and connection to your fleet through on-site and remote monitoring options. Our EMCP 4 control panel provides flexible options, with a user-friendly interface, putting your management and diagnostic tools in one. The EMCP 4.4 controller provides multi-generator set paralleling capability, giving you the ability to add generator sets to provide expanded capacity and generator set redundancy to match your requirements. No two power needs are the same, which is why we offer a broad range of accessories and bolt-on system expansion attachments. Find flexible packaging options to work with your spatial requirements and environmental conditions. Even select from UL 2200 and CSA certified package options for added safety. Our 3516C generator sets are built to take on power challenges — customize them to take on yours.

Generator Set Specifications

  • Minimum Rating 2500 kVA 2500 kVA
  • Maximum Rating 2750 kVA 2750 kVA
  • Voltage 220 to 13800 volts 220 to 13800 volts
  • Frequency 50 Hz 50 Hz
  • Speed 1500 RPM 1500 RPM

Generator Set Configurations

  • Emissions/Fuel Strategy U.S. EPA Certified for Stationary Emergency Use Only (Tier 2 Nonroad Equivalent Emission Standards), Low Fuel Consumption U.S. EPA Certified for Stationary Emergency Use Only (Tier 2 Nonroad Equivalent Emission Standards), Low Fuel Consumption

Engine Specifications

  • Engine Model 3516C, ATAAC, V-16,4-Stroke Water-Cooled Diesel 3516C, ATAAC, V-16,4-Stroke Water-Cooled Diesel
  • Compression Ratio 14.7:1 14.7:1
  • Aspiration TA TA
  • Governor Type Adem™3 Adem™3
  • Fuel System Electronic unit injection Electronic unit injection
  • Bore 6.69 in 170.0 mm
  • Stroke - HD 8.46 in 215.0 mm
  • Stroke - Standard 7.48 in 190.0 mm

3516C (50 Hz) Standard Equipment

Air Inlet

  • Air Cleaner

Cooling

  • Package mounted radiator

Exhaust

  • Exhaust flange outlet

Fuel

  • Primary fuel filter with integral water separator
  • Secondary fuel filter
  • Fuel priming pump

Generator

  • Matched to the performance and output characteristics of Cat engines
  • IP23 Protection

Power Termination

  • Bus Bar

Control Panel

  • EMCP 4 Genset Controller

General

  • Paint - Caterpillar Yellow except rails and radiators gloss black

3516C (50 Hz) Optional Equipment

Exhaust

  • Exhaust mufflers

Generator

  • Anti-condensation heater
  • Excitation: [ ] Permanent Magnet Excited (PM) [ ] Internally Excited (IE)
  • Oversize and premium generators

Power Termination

  • Circuit breakers, UL listed
  • Circuit breakers, IEC compliant

Control Panels

  • EMCP (4.2) (4.3) (4.4)
  • Generator temperature monitoring & protection
  • Load share module
  • Digital I/O module
  • Remote monitoring software

Mounting

  • Rubber anti-vibration mounts
  • Spring-type vibration isolator
  • IBC isolators

Starting/Charging

  • Battery chargers
  • Oversize batteries
  • Jacket water heater
  • Heavy-duty starting system
  • Charging alternator
  • Air starting motor with control and silencer

General

  • The following options are based on regional and product configuration:
  • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
  • UL 2200 package
  • EU Certificate of Conformance (CE)
  • CSA Certification
  • EEC Declaration of Conformity
  • Enclosures: sound attenuated, weather protective
  • Automatic transfer switches (ATS)
  • Integral & sub-base fuel tanks
  • Integral & sub-base UL listed dual wall fuel tanks

News & Events

View the latest company and product news, events and customer stories.

Promotions

View the latest offers available on a range of Cat® equipment and genuine parts.

Social Media

Connect with us to learn more about our company, products, services and customers.

Branch Locations

With branches across the UK & Ireland, you can be sure that we’re never far away.

Services

Effectively manage your equipment to reduce operating costs and improve efficiency.

Technology

Integrated technology can help you understand your equipment's output and help extend its lifespan.

Finance

Quick and easy financing with customised payment plans through Cat Financial.

Please share your feedback on Finning.com!

Close window

We are committed to providing you with the best site experience possible.  Please take our brief survey to tell us how we are doing.

Thank you in advance for your time!