Providing reliable energy solutions ,our C7.1 diesel generator sets are made to meet your standby and prime three phase applications. All standby C7.1 generator sets are supplied with 4 years extended service coverage as standard. We've designed each to ISO 8528-5 transient response requirements. C7.1 generator sets are available with a choice of emissions levels from non regulated up to EU Stage IIIA emissions compliant. We offer easy-to-use Cat control panels, EMCP 4.1 or EMCP 4.2 options. Browse a broad range of accessories including galvanised sound attenuated enclosures and integral fuel tanks. Our C7.1 generator sets are made for demands, so you can make yours.

Generator Set Specifications

  • Minimum Rating 135.0 kVA (108.0 ekW) 135.0 kVA (108.0 ekW)
  • Maximum Rating 218.0 kVA (174.4 ekW) 218.0 kVA (174.4 ekW)
  • Voltage 110 to 480 Volts 110 to 480 Volts
  • Frequency 50 Hz 50 Hz
  • Speed 1500 RPM 1500 RPM

Generator Set Configurations

  • Emissions/Fuel Strategy Non Regulated, EU Stage IIIA Non Regulated, EU Stage IIIA

Engine Specifications

  • Engine Model Cat® C7.1 Cat® C7.1
  • Compression Ratio 16.0:1, 18.2:1 16.0:1, 18.2:1
  • Aspiration Turbocharged, Air to Air Aftercooled Turbocharged, Air to Air Aftercooled
  • Governor Type Mechanical Mechanical
  • Fuel System Direct Injection Direct Injection
  • Bore 4.1 in 105.0 mm
  • Displacement 427.8 in³ 7.0 l
  • Stroke 5.3 in 135.0 mm

C7.1 (50 Hz) Standard Equipment

Air Inlet System

  • Air Cleaner; light duty with disposable element

Control Panels

  • EMCP4.1

Cooling System

  • Radiator and cooling fan with guards
  • Coolant drain line with valves
  • Fan drive, battery charging alternator drive
  • Caterpillar extended life coolant

Fuel System

  • Standard open set fuel tank / base supplied
  • Base, formed steel with single wall integral 8-hour fuel tank

Generator and Generator Attachments

  • 12 leads
  • IP23 protection
  • Voltage regulator (single phase sensing)
  • Tower panel, IP22, bottom cable entry
  • Segregated low voltage (AC/DC) wiring panel
  • Circuit breaker, IEC, 3 pole, mounted in tower panel

Governing System

  • Mechanical and electrical governing system - model dependent

Lube System

  • Lubricating oil
  • Oil drain line with valve

Mounting System

  • Captive linear vibration isolators between base and engine-generator
  • Includes lifting provision and drag points
  • Termination points for coolant and lube oil drain lines

Starting / Charging System

  • 24V battery with rack and cables

General

  • Engine and alternator pre-paint, Caterpillar Yellow

C7.1 (50 Hz) Optional Equipment

Alternator System

  • R frame auxiliary winding: R2273L4 SE aux alt 07, aux alt 08 and aux alt 10
  • Optional LC frame alternators
  • Optional LC frame alternator with coastal insulation protection
  • Permanent magnet
  • 3 Phase sensing
  • Quatrature droop king
  • Anti-condensation heater

Circuit Breakers

  • 4 Pole 250A, 400A and 630 A Circuit Breakers
  • Padlockable breaker device

Control System

  • EMCP 4.2

Control Panel Options

  • Volt free contacts
  • Speed adjust contacts
  • Speed adjust potentiometer
  • Panel mounted audible alarm
  • Earth fault (2 wire only)
  • Earth leakage (2 wire only)
  • Overload shutdown via breaker
  • Battery charger
  • Emergency stop with key
  • Control panel heater

Cooling System

  • Coolant heater
  • Low coolant temperature
  • Low coolant level shutdown

Enclosures

  • Sound attenuated level 2 enclosure
  • Sound attenuated level 1 enclosure
  • Rental options (CAE only) - Single point lift
  • Rental options (CAE only) - Rental pack
  • Rental options (CAE only) - CEE form sockets for enclosure
  • Rental options (CAE only) - Socket blanking plate

European Certifications

  • Upgrade to STD set for CE

Fuel Systems

  • Open set narrow tankbase
  • Compact skidbase for open sets
  • Skidbase for CALG enclosure sets
  • DEFRA bunded fuel tank
  • Low fuel level shutdown
  • Low fuel level alarm
  • High fuel level alarm

Global Certifications

  • Certification for CIS

Mounting Options

  • Electronic governor
  • Residential silencer
  • Silencer installation kit

Test Reports

  • PGS test report @ 1.0 power factor
  • PGS test report @ 0.8 power factor

General

  • Stone guards / radiator trans flange

News & Events

View the latest company and product news, events and customer stories.

Promotions

View the latest offers available on a range of Cat® equipment and genuine parts.

Social Media

Connect with us to learn more about our company, products, services and customers.

Branch Locations

With branches across the UK & Ireland, you can be sure that we’re never far away.

Services

Effectively manage your equipment to reduce operating costs and improve efficiency.

Technology

Integrated technology can help you understand your equipment's output and help extend its lifespan.

Finance

Quick and easy financing with customised payment plans through Cat Financial.

Please share your feedback on Finning.com!

Close window

We are committed to providing you with the best site experience possible.  Please take our brief survey to tell us how we are doing.

Thank you in advance for your time!